Zabezpieczenie termistorowe;siln.przek.przeciąż. EMT6(230V)

  • pcs.
  • Catalog price: 547.00 zł
  • (Catalog gross price: 672.81 zł)
  • Discount: -218.80 zł (40 %)
  • (Gross discount: -269.12 zł (40 %))
  • Gross price: 403.69 zł / pcs. 328.20 zł / pcs.
Zabezpieczenie termistorowe;siln.przek.przeciąż. EMT6(230V)
Program
Product range
  EMT6 thermistor overload relay for machine protection
Function
  Without automatic reset
Mains and fault LED display
Rated operational current
   
AC-15
   
240 V
IeA3
AC--14
   
400 V
IeA3
conventional thermal current
IthA6
Rated control voltage
UsV230 V 50/60 Hz
Notes

II (2) G

II (2) GD only for EMT6-K

Observe the manual AWB2327-1446 →#264853

Can be snap fitted on a top-hat rail to IEC/EN 60715.

Spacing of devices 3 mm.

1) EMT6, EMT6(230V), EMT6-DB and EMT6-DB(230V):an additional short-circuit protection in the sensor circuit with current monitor is to be provided.

Information relevant for export to North America

Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking

UL File No.E29184

UL CCNNKCR

CSA File No.012528

CSA Class No.3211-03

NA CertificationUL Listed, CSA certified

Approbationen
Product StandardsUL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No.E29184
UL CCNNKCR
CSA File No.12528
CSA Class No.3211-03
NA CertificationUL Listed, CSA certified
Specially designed for NANo
Max. Voltage Rating600 V AC
Degree of ProtectionIEC: IP20, UL/CSA Type: -
 
General
Standards
  IEC/EN 60947, VDE 0660, EN 55011
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
 °C 
Open
 °C-25- 60
Enclosed
 °C-25- 45
Storage
 °C-45- 60
Mounting position
  As required
Weight
 kg0.15
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
 g10
Protection type
  IP20
Protection against direct contact when actuated from front (EN 90274)
  Finger- and back-of-hand proof
Safe isolation to VDE 0106 Part 101 and Part 101/A1
   
between the contacts
 V AC250
between contacts and power supply
 V AC250
Auxiliary and control circuits
Rated impulse withstand voltage
UimpV AC6000
Overvoltage category/pollution degree
  III/3
Terminal capacities Auxiliary and control circuits
   
Solid
 mm21 x 2.5
2 x (0.5 - 1.5)
Flexible with ferrule
 mm21 x 2.5
2 x (0.5 - 1.5)
Solid or stranded
 AWG20 - 14
Terminal screw
  M3.5
Tightening torque
 Nm1.2
Tools
   
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm1 x 6
Auxiliary power circuit
Rated insulation voltage
UiV400
Rated operational current
IeA 
AC--14
   
Make contact
   
415 V
IeA3
Break contact
   
415 V
IeA3
AC-15
   
Make contact
   
240 V
IeA3
415 V
IeA1
Break contact
   
240 V
IeA3
415 V
IeA1
Max. short-circuit protective device
   
Fuse
gG/gLA6
Control circuit
Rated insulation voltage
UiV240
Rated operational voltage
UeV230
Pick-up and drop-out values
 x Ue0.85- 1.1
Power consumption
   
AC
 VA3.5
DC
 W2
Trip at approx.
 3600
Recovery at approx.
 1600
Notes
Notes EMT6(-DB)230V: Ue= 230 V
Technical data according to ETIM 4.0
Width
 mm23
Height
 mm83
Depth
 mm103
With detachable clamps
  No
Error registration possible
  No
Number of measuring circuits
  1
External reset possible
  No
Type of electric connection
  Screw connection
Rated control supply voltage Us at AC 50HZ
 V230
Rated control supply voltage Us at AC 60HZ
 V230
Rated control supply voltage Us at DC
 V0
Voltage type for actuation
  AC
Number of contacts as normally closed contact
  1
Number of contacts as normally open contact
  1
Number of contacts as change-over contact
  0
Dimensions

Opis pochodzi ze strony www.moeller.net .