Stycznik mocy z modułem 2Z2R 200kW/400V/AC3 DILM400/22(RA250)
Program
Approbationen
|
General | |||
Standards | IEC/EN 60947, VDE 0660, UL, CSA | ||
Lifespan, mechanical | |||
AC operated | Operations | x 106 | 7 |
DC operated | Operations | x 106 | 7 |
Operating frequency, mechanical | |||
AC operated | Operations/h | 2000 | |
DC operated | Operations/h | 2000 | |
Climatic proofing | Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 | ||
Ambient temperature | °C | ||
Open | °C | -25- 60 | |
Enclosed | °C | -25- 40 | |
Storage | °C | -40- 80 | |
Mounting position | |||
Mounting position, AC- and DC operated | |||
Mechanical shock resistance (IEC/EN 60068-2-27) | |||
Half-sinusoidal shock, 10 ms | |||
Main contacts | |||
N/O contact | g | 10 | |
Auxiliary contacts | |||
N/O contact | g | 10 | |
N/C contact | g | 8 | |
Protection type | IP00 | ||
Protection against direct contact when actuated from front (EN 90274) | finger and back-of-hand proof with terminal shroud or terminal block | ||
Weight | |||
AC operated | kg | 8 | |
DC operated | kg | 8 | |
Weight | kg | 8 | |
Terminal capacity main cable | |||
Flexible with cable lug | mm2 | 50 - 240 | |
Stranded with cable lug | mm2 | 70 - 240 | |
Solid or stranded | AWG | 2/0 - 500 MCM | |
Flat conductor | Number of segments x width x thickness | mm | Fixing with flat cable terminal or cable terminal blocks See terminal capacity for cable terminal blocks |
Busbar | Width | mm | 25 |
Main cable connection screw/bolt | M10 | ||
Tightening torque | Nm | 24 | |
Terminal capacity control circuit cables | |||
Solid | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) | |
Flexible with ferrule | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) | |
Solid or stranded | AWG | 2 x (18 - 12) | |
Control circuit cable connection screw/bolt | M3.5 | ||
Tightening torque | Nm | 1.2 | |
Tool | |||
Main cable | |||
Open-end spanner | mm | 16 | |
Control circuit cables | |||
Pozidriv screwdriver | Size | 2 | |
Main conducting paths | |||
Rated impulse withstand voltage | Uimp | V AC | 8000 |
Overvoltage category/pollution degree | III/3 | ||
Rated insulation voltage | |||
AC | Ui | V AC | 1000 |
Rated operational voltage | Ue | V AC | 1000 |
Safe isolation to VDE 0106 Part 101 and Part 101/A1 | |||
between coil and contacts | V AC | 500 | |
between the contacts | V AC | 500 | |
Making capacity (p.f. to IEC/EN 60947) | A | 5500 | |
Breaking capacity | |||
220/230 V | A | 5000 | |
380/400 V | A | 5000 | |
500 V | A | 5000 | |
660/690 V | A | 5000 | |
1000 V | A | 950 | |
Short-circuit rating | |||
Short-circuit protection maximum fuse | |||
Type “2” coordination | |||
400 V | gG/gL 500 V | A | 500 |
690 V | gG/gL 690 V | A | 500 |
1000 V | gG/gL 1000 V | A | 200 |
Type “1” coordination | |||
400 V | gG/gL 500 V | A | 630 |
690 V | gG/gL 690 V | A | 630 |
1000 V | gG/gL 1000 V | A | 250 |
AC | |||
AC-1 duty | |||
Conventional free air thermal current, 3 pole, 50 - 60 Hz | |||
Open | |||
at 40 °C | Ith =Ie | A | 612 |
at 50 °C | Ith =Ie | A | 548 |
at 55 °C | Ith =Ie | A | 522 |
at 60 °C | Ith =Ie | A | 500 |
enclosed | Ith | A | 450 |
Conventional free air thermal current, 1 pole | |||
open | Ith | A | 1250 |
enclosed | Ith | A | 1125 |
AC-3 duty | |||
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole | Ie | ||
220/230 V | Ie | A | 400 |
240 V | Ie | A | 400 |
380/400 V | Ie | A | 400 |
415 V | Ie | A | 400 |
440V | Ie | A | 400 |
500 V | Ie | A | 400 |
660/690 V | Ie | A | 360 |
1000 V | Ie | A | 95 |
Motor rating | P | kWh | |
220/230 V | P | kW | 125 |
240V | P | kW | 132 |
380/400 V | P | kW | 200 |
415 V | P | kW | 240 |
440 V | P | kW | 200 |
500 V | P | kW | 290 |
660/690 V | P | kW | 344 |
1000 V | P | kW | 132 |
AC-4 duty | |||
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole | Ie | ||
220/230 V | Ie | A | 296 |
240 V | Ie | A | 296 |
380/400 V | Ie | A | 296 |
415 V | Ie | A | 296 |
440 V | Ie | A | 296 |
500 V | Ie | A | 296 |
660/690 V | Ie | A | 296 |
1000 V | Ie | A | 95 |
Motor rating | P | kWh | |
220/230 V | P | kW | 92 |
240 V | P | kW | 101 |
380/400 V | P | kW | 160 |
415 V | P | kW | 176 |
440 V | P | kW | 186 |
500 V | P | kW | 214 |
660/690 V | P | kW | 283 |
1000 V | P | kW | 132 |
Condensor operation | |||
Individual compensation, rated operational current Ieof three-phase capacitors | |||
open | |||
up to 525 V | A | 307 | |
690 V | A | 177 | |
Max. inrush current peak | x Ie | 30 | |
Component lifespan | Operations | x 106 | 0.1 |
Max. operating frequency | Ops/h | 200 | |
DC | |||
Rated operational current, open | |||
DC-1 operation | |||
60 V | Ie | A | 400 |
110 V | Ie | A | 400 |
220 V | Ie | A | 400 |
440 V | Ie | A | 11 |
DC-3 operation | |||
60 V | Ie | A | 400 |
110 V | Ie | A | 400 |
220 V | Ie | A | 400 |
DC-5 operation | |||
60 V | Ie | A | 400 |
110 V | Ie | A | 400 |
220 V | Ie | A | 400 |
Current heat loss (3 pole) | |||
Current heat loss at Ith | W | 58 | |
Current heat loss at Ieto AC-3/400 V | W | 37 | |
Magnet systems | |||
Voltage tolerance | x Uc | ||
UC | 110 - 250 V 40-60 Hz 110 - 250 V DC | ||
AC operated | Pick-up | x Uc | |
Pick-up | x Uc | 0.7 x Uc min- 1.15 x Uc max | |
DC operated | Pick-up | x Uc | |
Pick-up | x Uc | 0.7 x Uc min- 1.15 x Uc max | |
Drop-out voltage AC operated | Drop-out | x Uc | |
Drop-out | x Uc | 0.2 x Uc min- 0.6 x Uc max | |
DC operated | Drop-out | x Uc | |
Drop-out | x Uc | 0.2 x Uc min- 0.6 x Uc max | |
Power consumption of the coil in a cold state and 1.0 x Uc | |||
50 Hz | Pick-up | VA | 450 |
AC operated | Pick-up | W | 350 |
60 Hz | Pick-up | VA | 715 |
60 Hz | Pick-up | W | 645 |
Dual-frequency coil 50/60 Hz at 50 Hz | Sealing | VA | 4.3 |
Dual-frequency coil 50/60 Hz at 50 Hz | Sealing | W | 3.3 |
Dual-frequency coil 50/60 Hz at 60 Hz | Sealing | VA | 4.3 |
Dual-frequency coil 50/60 Hz at 60 Hz | Sealing | W | 3.3 |
Duty factor | % DF | 100 | |
Switching times at 100 % Uc(approximate values) | |||
Main contacts | |||
AC operated | |||
Closing delay | ms | 80 | |
Opening delay | ms | 110 | |
DC operated | ms | ||
Closing delay | ms | 55 | |
Opening delay | ms | 50 | |
Behaviour in marginal and transitional conditions | |||
Sealing | |||
Voltage interruptions | |||
(0 … 0.2 x Uc min) 10 ms | Time is bridged successfully | ||
(0 … 0.2 x Uc min) > 10 ms | Drop-out of the contactor | ||
Voltage drops | |||
(0.2 … 0.6 x Uc min) 12 ms | Time is bridged successfully | ||
(0.2 … 0.6 x Uc min) > 12 ms | Drop-out of the contactor | ||
(0.6 … 0.7 x Uc min) | Contactor remains switched on | ||
Excess voltage | |||
(1.15 … 1.3 x Uc max) | Contactor remains switched on | ||
(> 1.3 x Uc max) 3 s | Contactor remains switched on | ||
(> 1.3 x Uc max) > 3 s | Drop-out of the contactor | ||
Pick-up phase | |||
(0 … 0.7 x Uc min) | Contactor does not switch on | ||
(0.7 x Uc min … 1.15 x Uc max) | Contactor switches on with certainty | ||
(> 1.15 x Uc max) | Contactor switches on with certainty | ||
Admissible transitional contact resistance(of the external control circuit device when actuating A11) | mΩ | 500 | |
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2) | |||
High | V | 15 | |
Low | V | 5 | |
Electromagnetic compatibility (EMC) | |||
Electromagnetic compatibility | This product is designed for operation in industrial environments (environment 2). The use in residential environments (environment 1) could cause electrical interference so that addition suppression must be planned. |
Technical data according to ETIM 4.0
Number of main contacts as N/Os | 3 | ||
Rated operation current Ie at AC-1, 400 V | 612 | ||
Connection type main circuit | Screw connection | ||
Rated control voltage Us at AC 60HZ | V | 250 | |
Number of auxiliary contacts as N/Os | 2 | ||
Rated control voltage Us at AC 50HZ | V | 250 | |
Number of auxiliary contacts as N/Cs | 2 | ||
Suitable for rail-mounting | No | ||
Rated control voltage Us at DC | V | 250 | |
Voltage type for actuation | AC/DC | ||
Rated operation current Ie at AC-3, 400 V | A | 400 | |
Number of N/Cs as main contact | 0 | ||
Motor rating at AC-3, 400 V | kWh | 200 |
Characteristics
on the side: 2 x DILM820-XHI(V)11-SI; 2 x DILM820-XHI(V)11-SA | |||
→ operating frequency | |||
Squirrel-cage motor Operating characteristics Starting:from rest Stopping:after attaining full running speed Electrical characteristics Make: up to 6 x rated motor current Break: up to 1 x rated motor current Utilization category 100 % AC-3 Typical applications Compressors Lifts Mixers Pumps Escalators Agitators Fans Conveyor belts Centrifuges Hinged flaps Bucket-elevators Air conditioning system General drives in manufacturing and processing machines | |||
Extreme switching duty Squirrel-cage motor Operating characteristics Inching, plugging, reversing Electrical characteristics Make: up to 6 x rated motor current Break: up to 6 x rated motor current Utilization category 100 % AC-4 Typical applications Printing presses Wire-drawing machines Centrifuges Special drives for manufacturing and processing machines | |||
Switching duty for non-motor loads, 3-pole, 4-pole Operating characteristics Non-inductive or slightly inductive loads Electrical characteristics Make: 1 x rated current Break: 1 x rated current Utilization category 100 % AC-1 Typical applications Electric heat | |||
Short-time loading, 3-pole Time interval between two loading cycles: 15 minutes | |||
Normal switching duty |
CAD-Data
|
Additional product information (links)
IL03406002Z (AWA2100-1639) contactors | |||
Installation Instructions | |||
Documentation | |||
Motor starters and "Special Purpose Ratings" for the North American market | |||
Busbar Component Adapters for modern Industrial control panels | |||
The Interaction of Contactors with PLCs | |||
Standard Compliant and Functionally Safe Engineering Design with Mechanical Auxiliary Contacts | |||
Switchgear for Luminaires | |||
Effect of the Cabel Capacitance of Long Control Cables on the Actuation of Contactors | |||
X-Start - Modern Switching Installations Efficiently Fitted and Wired Securely | |||
Mirror Contacts for Highly-Reliable Information Relating to Safety-Related Control Functions | |||
X-Start - New Generation:100 years of Moeler contactors - Continous Progress- | |||
Switchgear of Power Factor Correction Systems |
Opis pochodzi ze strony www.moeller.net .