Stycznik mocy, 1000 A (560kW), AC-3, 400

  • szt.
  • Discount: -11,007.60 zł (40 %)
  • (Gross discount: -13,539.35 zł (40 %))
  • Gross price: 20,309.02 zł / szt. 16,511.40 zł / szt.
Stycznik mocy, 1000 A (560kW), AC-3, 400 V DILM1000/22(RA250)
Program
Product range
  Contactors
Application
  Contactors for Motors
Subrange
  Comfort devices greater than 150 A
Connection technique
  Screw terminals
Rated operational current
   
AC-3
   
380 V 400 V
IeA1000
AC-1
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 60 °C
Ith =IeA1000
Max. rating for three-phase motors, 50 - 60 Hz
   
AC-3
   
220 V 230 V
PkW315
380 V 400 V
PkW560
660 V 690 V
PkW1000
1000 V
PkW1100
AC-4
   
220 V 230 V
PkW260
380 V 400 V
PkW450
660 V 690 V
PkW780
1000 V
PkW1000
Contact sequence
  
Actuating voltage
  RA 250: 110-250 V 40-60 Hz/110-250 V DC
Contacts
   
N/O = Normally open
  2 N/O
N/C = Normally closed
  2 B
Auxiliary contacts
   
possible variants at auxiliary contact module fitting options
  on the side: 2 x DILM820-XHI(V)11-SI; 2 x DILM820-XHI(V)11-SA
Side mounting auxiliary contacts
  
Instructions
  integrated suppressor circuit in actuating electronics
660 V, 690 V or 1000 V: not directly reversing
Note concerning the product
ClassicalDILM185A, DILM225ADILM250 to DILM1000, DILH1400DILM1600, DILH2000, DILH2600
A1/A2 are attached to power supply as normal
Direct from the PLC
A 3 V output from the PLC can be directly connected to the connections A4/A24.
From a low-power actuating device
Low-power actuating devices such as PCB relays, actuating devices or position switches can be directly connected to A10/A11.

Stopping in the event of an emergency (emergency switching off)

Max. capacity 6 nF

Notes

During a high voltage test for the contactors DILM580 to DILH2600 the suppressor circuit on the load side must be removed.

Control voltages

RA250 110 V - 250 V AC/DC

RAW250 230 V - 250 V AC/DC

Approbationen
Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.E29096
UL CCNNLDX
CSA File No.012528
CSA Class No.3211-04
NA CertificationUL Listed, CSA certified
Specially designed for NANo
 
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 1065
DC operated
Operationsx 1065
Operating frequency, mechanical
   
AC operated
Operations/h 1000
DC operated
Operations/h 1000
Climatic proofing
  Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature
 °C 
Open
 °C-25- 60
Enclosed
 °C-25- 40
Storage
 °C-40- 80
Mounting position
  
Mounting position, AC- and DC operated
  

Mechanical shock resistance (IEC/EN 60068-2-27)
   
Half-sinusoidal shock, 10 ms
   
Main contacts
   
N/O contact
 g10
Auxiliary contacts
   
N/O contact
 g10
N/C contact
 g8
Protection type
  IP00
Protection against direct contact when actuated from front (EN 90274)
  finger and back-of-hand proof with terminal shroud or terminal block
Weight
   
AC operated
 kg15
DC operated
 kg15
Weight
 kg15
Terminal capacity main cable
   
Flexible with cable lug
 mm250 - 240
Stranded with cable lug
 mm270 - 240
Solid or stranded
 AWG2/0 - 500 MCM
Busbar
Widthmm60
Main cable connection screw/bolt
  M12
Tightening torque
 Nm35
Terminal capacity control circuit cables
   
Solid
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
 mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded
 AWG2 x (18 - 12)
Control circuit cable connection screw/bolt
  M3.5
Tightening torque
 Nm1.2
Tool
   
Main cable
   
Open-end spanner
 mm18
Control circuit cables
   
Pozidriv screwdriver
 Size2
Main conducting paths
Rated impulse withstand voltage
UimpV AC8000
Overvoltage category/pollution degree
  III/3
Rated insulation voltage
   
AC
UiV AC1000
Rated operational voltage
UeV AC1000
Safe isolation to VDE 0106 Part 101 and Part 101/A1
   
between coil and contacts
 V AC500
between the contacts
 V AC500
Making capacity (p.f. to IEC/EN 60947)
 A9840
Breaking capacity
   
220/230 V
 A8200
380/400 V
 A8200
500 V
 A8200
660/690 V
 A8200
1000 V
 A5800
Short-circuit rating
   
Short-circuit protection maximum fuse
   
Type “2” coordination
   
400 V
gG/gL 500 VA 630
690 V
gG/gL 690 VA 630
1000 V
gG/gL 1000 VA 630
Type “1” coordination
   
400 V
gG/gL 500 VA 1200
690 V
gG/gL 690 VA 1200
1000 V
gG/gL 1000 VA 800
AC
AC-1 duty
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
Open
   
at 40 °C
Ith =IeA1225
at 50 °C
Ith =IeA1095
at 55 °C
Ith =IeA1044
at 60 °C
Ith =IeA1000
Conventional free air thermal current, 1 pole
   
open
IthA2500
AC-3 duty
   
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole
Ie  
220/230 V
IeA1000
240 V
IeA1000
380/400 V
IeA1000
415 V
IeA1000
440V
IeA1000
500 V
IeA1000
660/690 V
IeA1000
1000 V
IeA750
Motor rating
PkWh 
220/230 V
PkW315
240V
PkW340
380/400 V
PkW560
415 V
PkW610
440 V
PkW650
500 V
PkW730
660/690 V
PkW1000
1000 V
PkW1100
AC-4 duty
   
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole
Ie  
220/230 V
IeA800
240 V
IeA800
380/400 V
IeA800
415 V
IeA800
440 V
IeA800
500 V
IeA800
660/690 V
IeA800
1000 V
IeA700
Motor rating
PkWh 
220/230 V
PkW260
240 V
PkW280
380/400 V
PkW450
415 V
PkW490
440 V
PkW520
500 V
PkW590
660/690 V
PkW780
1000 V
PkW1000
Condensor operation
Individual compensation, rated operational current Ieof three-phase capacitors
   
open
   
up to 525 V
 A463
690 V
 A265
Max. inrush current peak
 x Ie30
Component lifespan
Operationsx 1060.1
Max. operating frequency
 Ops/h200
Current heat loss (3 pole)
Current heat loss at Ith
 W96
Current heat loss at Ieto AC-3/400 V
 W96
Magnet systems
Voltage tolerance
 x Uc 
UC
  110 - 250 V 40-60 Hz
110 - 250 V DC
AC operated
Pick-upx Uc 
 
Pick-upx Uc0.7 x Uc min- 1.15 x Uc max
DC operated
Pick-upx Uc 
 
Pick-upx Uc0.7 x Uc min- 1.15 x Uc max
Drop-out voltage AC operated
Drop-outx Uc 
 
Drop-outx Uc0.2 x Uc min- 0.6 x Uc max
DC operated
Drop-outx Uc 
 
Drop-outx Uc0.2 x Uc min- 0.6 x Uc max
Power consumption of the coil in a cold state and 1.0 x Uc
   
Note on power consumption
  Control transformer with uk0.7
50 Hz
Pick-upVA800
AC operated
Pick-upW700
Dual-frequency coil 50/60 Hz at 50 Hz
SealingVA7.5
Dual-frequency coil 50/60 Hz at 50 Hz
SealingW6.5
Duty factor
 % DF100
Switching times at 100 % Uc(approximate values)
   
Main contacts
   
AC operated
   
Closing delay
 ms70
Opening delay
 ms110
Behaviour in marginal and transitional conditions
   
Sealing
   
Voltage interruptions
   
(0 … 0.2 x Uc min) 10 ms
  Time is bridged successfully
(0 … 0.2 x Uc min) > 10 ms
  Drop-out of the contactor
Voltage drops
   
(0.2 … 0.6 x Uc min) 12 ms
  Time is bridged successfully
(0.2 … 0.6 x Uc min) > 12 ms
  Drop-out of the contactor
(0.6 … 0.7 x Uc min)
  Contactor remains switched on
Excess voltage
   
(1.15 … 1.3 x Uc max)
  Contactor remains switched on
(> 1.3 x Uc max) 3 s
  Contactor remains switched on
(> 1.3 x Uc max) > 3 s
  Drop-out of the contactor
Pick-up phase
   
(0 … 0.7 x Uc min)
  Contactor does not switch on
(0.7 x Uc min … 1.15 x Uc max)
  Contactor switches on with certainty
(> 1.15 x Uc max)
  Contactor switches on with certainty
Admissible transitional contact resistance(of the external control circuit device when actuating A11)
 mΩ500
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)
   
High
 V15
Low
 V5
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
  This product is designed for operation in industrial environments (environment 2). The use in residential environments (environment 1) could cause electrical interference so that addition suppression must be planned.
Technical data according to ETIM 4.0
Number of main contacts as N/Os
  3
Rated operation current Ie at AC-1, 400 V
  1225
Connection type main circuit
  Screw connection
Rated control voltage Us at AC 60HZ
 V250
Number of auxiliary contacts as N/Os
  2
Rated control voltage Us at AC 50HZ
 V250
Number of auxiliary contacts as N/Cs
  2
Suitable for rail-mounting
  No
Rated control voltage Us at DC
 V250
Voltage type for actuation
  AC/DC
Rated operation current Ie at AC-3, 400 V
 A1000
Number of N/Cs as main contact
  0
Motor rating at AC-3, 400 V
 kWh560
Characteristics
on the side: 2 x DILM820-XHI(V)11-SI; 2 x DILM820-XHI(V)11-SA
Form for ordering non-standard front plates
Form for ordering non-standard switches
operating frequency
Squirrel-cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 1 x rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket-elevators
Air conditioning system
General drives in manufacturing and processing machines
Switching duty for non-motor loads, 3-pole, 4-pole
Operating characteristics
Non-inductive or slightly inductive loads
Electrical characteristics
Make: 1 x rated current
Break: 1 x rated current
Utilization category
100 % AC-1
Typical applications
Electric heat
Short-time loading, 3-pole
Time interval between two loading cycles: 15 minutes
Normal switching duty
Dimensions
DILM1000-XHI…-SI
DILM1000-XHI11-SA

Opis pochodzi ze strony www.moeller.net .