Rozłącznik mocy 3-bieg. 400A

  • szt.
  • Discount: -1,464.24 zł (40 %)
  • (Gross discount: -1,801.01 zł (40 %))
  • Gross price: 2,701.52 zł / szt. 2,196.36 zł / szt.

Rozłącznik mocy 3-bieg. 400A PN3-400

Program
Range
    Switch-disconnectors
Protective function
    Disconnectors/main switches
Standard/Approval
    IEC
Installation type
    Fixed mounted
Construction size
    PN3
Description
    Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
Busbar tag shroud to VDE 0160 Part 100.
Number of conductors
    3 pole
Standard equipment
    Screw connection
Switch positions
    I, 0
Rated current = rated uninterrupted current
In= Iu A 400
Short-circuit protection max. fuse gL-characteristic
  A gL 630
 
Switch-disconnectors
Rated surge voltage invariability
Uimp    
Main contacts
  V 8000
Auxiliary contacts
  V 6000
Rated operational voltage
Ue V AC 690
Rated current = rated uninterrupted current
In= Iu A 400
Rated uninterrupted current
Iu A  
IEC/EN 61131-3
Iu A 630
Overvoltage category/pollution degree
    III/3
Rated insulation voltage
Ui V 1000
For use in IT electrical power networks
  V 690
 
    Rated operating voltage: 40-60 Hz
Other technical data (sheet catalogue)
    Weight
Temperature dependency, Derating
Effective power loss
Rated short-circuit making capacity
690 V 50/60 H
Ic kA 25
Rated short-time withstand current
t = 0.3 s
Icw kA 12
t = 1 s
Icw kA 12
Rated conditional short-circuit current
With back-up fuse
  A gG/gL PN3(N3)-400…630: 630
400 … 415 V
  kA 100
690 V
  kA 80
With downstream fuse
  A gG/gL PN3(N3)-400…630: 630
400 … 415 V
  kA 100
690 V
  kA 80
Rated making and breaking capacity
Rated operational current
Ie A  
415 V
Ie A 630
690 V
Ie A 630
415 V
Ie A 630
690 V
Ie A 630
Lifespan, mechanical
Operations   15000
Max. operating frequency
  Ops/h 60
Lifespan, electrical
400 V V 50/60 Hz
Operations   5000
415 V V 50/60 Hz
Operations   5000
690 V 50/60 Hz
Operations   3000
400 V 50/60 Hz
Operations   3000
415 V 50/60 Hz
Operations   3000
690 V 50/60 Hz
Operations   2000
Current heat losses per pole at Iuare based on the maximum rated operational current of the frame size.
  W 40
Total downtime in a short-circuit
  ms < 10
Terminal capacity
Standard equipment
    Screw connection
Overview
   
Basic equipment                
  Box terminal     -   -   -
  Screw connection   -      
Accessories                
  Box terminal   -       -
  Screw connection     -   -  
  Tunnel terminal        
  Connection on rear        
  Flat conductor terminal   -   -   -  
Round copper conductor
     
Box terminal
     
Solid
  mm2 2 x 16
Stranded
  mm2 1 x (35 - 240)
2 x (25 - 120)
Tunnel terminal
     
Solid
  mm2 1 x (16 - 185)
Stranded
  mm2  
Stranded
  mm2 1 x (25 - 185)
Double hole fitting
  mm2 1 x (50 - 240)
2 x (50 - 240)
Bolt terminal and rear-side connection
     
Direct on the switch
     
Solid
  mm2 1 x 16
2 x 16
Stranded
  mm2 1 x (25 - 240)
2 x (25 - 240)
Connection width extension
  mm2  
Connection width extension
  mm2 2 x 300
Al conductors, Cu cable
     
 
     
Solid
  mm2 1 x 16
Stranded
  mm2  
Stranded
  mm2 1 x (25 - 185)
In base alla casa produttrice dei cavi, collegabile fino a 240 mm²
Double hole fitting
  mm2 1 x (50 - 240)
2 x (50 - 240)
Bolt terminal and rear-side connection
     
Flat copper strip, with holes
min. mm 6 x 16 x 0.8
Flat copper strip, with holes
max. mm 10 x 32 x 1.0 + 5 x 32 x 1.0
Connection width extension
  mm2 (2 x) 10 x 50 x 1.0
Cu strip (number of segments x width x segment thickness)
     
Box terminal
     
 
min. mm2 6 x 16 x 0.8
 
max. mm2 10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0
Bolt terminal and rear-side connection
     
Flat copper strip, with holes
min. mm 6 x 16 x 0.8
Flat copper strip, with holes
max. mm 10 x 32 x 1.0 + 5 x 32 x 1.0
Connection width extension
  mm2 (2 x) 10 x 50 x 1.0
Copper busbar (width x thickness)
mm    
Bolt terminal and rear-side connection
     
Screw connection
    M10
Direct on the switch
     
 
min. mm2 20 x 5
 
max. mm2 30 x 10
+ 30 x 5
Connection width extension
  mm2  
Connection width extension
max. mm2 2 x (10 x 50)
Control cables
     
 
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Technical data according to ETIM 4.0
Number of auxiliary contacts as normally open contact
    0
Number of auxiliary contacts as normally closed contact
    0
Rated permanent current Iu
  A 400
Number of poles
    3
Conditioned rated short-circuit current Iq
  kA 100
Degree of protection (IP), front side
    IP20
Number of auxiliary contacts as change-over contact
    0
Interlockable
    YES
Motor drive integrated
    No
Connection type main current circuit
    Screw connection
Version as emergency stop installation
    No
Type of control element
    Toggle lever
Version as main switch
    No
Version as switch disconnector compact
    YES
Version as safety switch
    No
Version as maintenance-/service switch
    No
Rated operation power at AC-23, 400V
  kWh 0
Rated operation power AC-3, 400 V
  kWh 0
Suitable for ground mounting
    No
Suitable for front mounting
    No
Suitable for front mounting center
    No
Suitable for distribution board installation
    YES
Suitable for intermediate mounting
    No
Max. rated operation voltage Ue AC
  V 690
Motor drive optional
    YES
Voltage release optional
    YES
Device construction
    Built-in device fixed built-in technique
Dimensions
Blow out area, minimum clearance to adjacent parts
Minimum clearance to adjacent parts

Opis pochodzi ze strony www.moeller.net .