Cyfrowy Moduł wej./wyj. 16x24VDC
- szt.
- Discount: -1,562.00 zł (40 %)
- (Gross discount: -1,921.26 zł (40 %))
- Gross price: 2,881.89 zł / szt. 2,343.00 zł / szt.
Cyfrowy moduł wej./wyj. 16x24VDC XIOC-16DX
Program
|
Digital modules | ||
|
Compact I/O system for connection to XC100/200 Modular PLCs XC100/200 expandable with up to 15 XI/OC modules Optionally, screw terminals or spring-loaded terminals for digital/analog modules |
||
Description
|
16 connections, 4 inputs, 12 freely parameterizable as inputs/outputs, 24 V DC outputs 0.5 A | ||
Information relevant for export to North America
Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking UL File No.E29184 UL CCNNKCR CSA File No.012528 CSA Class No.3211-03 NA CertificationUL Listed, CSA certified |
Approbationen
|
General | |||
Standards
|
IEC/EN 61131-2 EN 50178 |
||
Ambient temperature
|
°C | 0 - +55 | |
Storage
|
°C | -25 - +70 | |
Vibration resistance
|
10 - 57 Hz ±0.075 mm 57 - 150 Hz ±1.0 mm |
||
Mechanical shock resistance
|
g | 15 Shock duration 11 ms |
|
Impact resistance
|
500 g/50 mm ±25 g | ||
Overvoltage category/pollution degree
|
II/2 | ||
Protection class
|
1 | ||
Protection type
|
IP20 | ||
Emitted interference
|
DIN/EN 55011/22, Class A | ||
Weight
|
kg | 0.16 | |
Power supply | |||
Rated voltage
|
Ue | V DC | 24 (12) |
Admissible range
|
20.4 – 28.8 (11.8 – 14.4) | ||
Neutral poles
|
|||
Duration of dip
|
ms | 10 | |
Repetition rate
|
s | 1 | |
Residual ripple
|
% | 5 | |
Supply voltage
|
24 V DC (-15/+20%) | ||
Overvoltage protection
|
Yes | ||
Protection against polarity reversal
|
Yes | ||
Potential isolation
|
|||
Power supply against I/O bus
|
Yes | ||
Power supply against I/O
|
No | ||
Internal current consumption (5 V DC)
|
mA | Normally 80 | |
Terminations
|
Plug-in terminal block | ||
Status indication
|
LED | ||
Inputs | |||
Input type
|
DC input | ||
Input voltage
|
V DC | 24 | |
Input current
|
mA | Normally 4 | |
Voltage level to IEC 61131-2, limit value type 1
|
|||
ON
|
V | 15 DC | |
OFF
|
V | 5 DC | |
Input delay
|
|||
Off → On
|
ms | Normally 0.1 | |
On → Off
|
ms | Normally 0.1 | |
Inputs
|
Number | 4, 12, configurable | |
Channels with the same reference potential
|
Number | 16 | |
Outputs | |||
Output type
|
Transistor (source type) | ||
Output voltage
|
V DC | 12/24 (-15…+20 %) | |
Output current
|
A | Normally 0.5 | |
Outputs
|
Number | Max. 12, configurable | |
Channels with the same reference potential
|
Qty. | 16 | |
Overvoltage protection
|
Yes | ||
Short-circuit tripping current
|
A | max. 1.2 over 3 ms per output | |
Lamp load
|
W | Max. 3 | |
Off-delay (High → Low)
|
µs | Normally 100 | |
Switching capacity
|
IEC/EN 60947-5-1, utilization category DC-13 | ||
Short-circuit rating
|
Yes | ||
Terminations
|
Plug-in terminal block | ||
Internal current consumption (5 V DC)
|
mA | 80 | |
Parallel connection of outputs
|
in groups 0 - 3, 4 - 7, 8 - 11; Actuation of the outputs within a group only in the same program cycle |
||
Number of outputs that can be switched in parallel
|
3 max. | ||
Total max. current
|
A | 2 per group |
Technical data according to ETIM 4.0
Short-circuit protective device, outputs available
|
YES | ||
Number of inputs
|
12 | ||
Number of outputs
|
12 | ||
Input current at signal 1
|
mA | 4 | |
Delay time on signal change
|
ms | 0.1 | |
Output current
|
A | 0.5 | |
Depth
|
mm | 95 | |
Height
|
mm | 100 | |
Width
|
mm | 30 |
Opis pochodzi ze strony www.moeller.net .