Zabezpieczenie transformatorów 3-bieg. PKZM0-1,6-T

  • szt.
  • Cena brutto: 427,92 zł 347,90 zł

Zabezpieczenie transformatorów 3-bieg. PKZM0-1,6-T

Program
Product range
    PKZM0...T transformer-protective circuit-breakers up to 25 A
Basic function
    Transformer protection
Connection technique
    Screw terminals
Contact sequence
   
Rated uninterrupted current
Iu A 1.6
Setting range
     
Overload releases
Ir A 1- 1.6
Short-circuit releases
     
max.
Irm A 32
Notes
For the protection of transformers with a high inrush current
can be snap-fitted to IEC/EN 60715 top-hat rail with 7.,5 or 15 mm height
Phase failure sensitivity to IEC/EN 60947-4-1, VDE 0660 part 102.
Approbationen
Specially designed for NA No
 
General
Standards
    IEC/EN 60947, VDE 0660
Climatic proofing
    Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature
  °C  
Storage
  °C -25- 80
Open
  °C -25- 55
Enclosed
  °C -25- 40
Mounting position
   
Direction of incoming supply
    As required
Degree of protection
     
Device
    IP20
Terminations
    IP00
Protection against direct contact
    Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
  g 25
Altitude
  m 2000
Terminal capacity screw terminals
  mm2  
Solid
  mm2 1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
  mm2 1 x (1 - 6)
2 x (1 - 6)
Solid or stranded
  AWG 18 - 10
Specified tightening torque for terminal screws
     
Main cable
  Nm 1.7
Control circuit cables
  Nm 1
Main conducting paths
Rated impulse withstand voltage
Uimp V AC 6000
Overvoltage category/pollution degree
    III/3
Rated operational voltage
Ue V AC 690
Rated uninterrupted current = rated operational current
Iu= Ie A 25 or current setting of the overcurrent release
Rated frequency
f Hz 40 - 60
Rated frequency
  Hz 40- 60
Current heat loss (3 pole at operating temperature)
  W 6
Lifespan, mechanical
Operations x 106 0.1
Lifespan, electrical (AC-3 at 400 V)
Operations x 106 0.1
Maximum operating frequency
  Ops./h  
Max. operating frequency
  Ops/h 40
Short-circuit rating
     
AC
     
 
    → Engineering
DC
     
Short-circuit rating
  kA 60
Short-circuit rating
    60 (up to PKZM0-16)
40 (PKZM0-20 to PKZM0-32)
Motor switching capacity
  kArms  
AC-3 (up to 690 V)
  A 25
DC-5 (up to 250 V)
  A 25 (3 contacts in series)
Trip blocks
Temperature compensation
     
to IEC/EN 60947, VDE 0660
  °C -5…40
Operating range
  °C -25…55
Temperature compensation residual error for T > 40 °C
    0.25%/K
Setting range of overload releases
  x Iu 0.6- 1
Short-circuit release fixed
  x Iu 20
Fixed short-circuit release
    Basic device 20 x Iu
Short-circuit release tolerance
    ± 20%
Phase-failure sensitivity
    IEC/EN 60947-1-1, VDE 0660 Part 102
Technical data according to ETIM 4.0
Number of poles
    3
Rated uninterrupted current Iu
  A 1.6
Number of auxiliary contacts as N/Cs
    0
Number of auxiliary contacts as N/Os
    0
Device construction
    -
With under voltage release
    No
Motor operator optional
    No
Integrated earth fault protection
    No
Suitable for DIN rail (top hat rail) mounting
    YES
Setting range non-delayed short-circuit release
  A 32
Setting range short-term delayed short-circuit release
  A 0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
  kA 150
Switched-off indicator available
    YES
Type of control element
    Rotary head
Connection type main current circuit
    Screw connection
Motor operator integrated
    YES
Position of connection for main circuit
    -
Protection type (IP)
    IP20
Number of auxiliary contacts as changeover contact
    0
Setting range of overload releases
  A 1.6
Characteristics
Motor-protective circuit-breaker tripping characteristic (high-capacity) compact starter, PKZM0-…T (not for PKM0-…), PKZM01
Let-through characteristics
Dimensions
Motor-protective circuit-breaker with standard auxiliary contact
PKZM0-…(+NHI-E-…-PKZ0)
PKZM0-…-T(+NHI-E-…-PKZ0)
PKM0-…(+NHI-E-…-PKZ0)
Motor-protective circuit-breakers with lockable rotary handles
PKZM0-…+AK-PKZ0
Motor-protective circuit-breakers with early-make auxiliary contacts
PKZM0-…+VHI-…-PKZ0

Opis pochodzi ze strony www.moeller.net .