Zabezpieczenie transformatorów 3-bieg. PKZM0-1,6-T
- Dodaj recenzję:
- Kod: 088912
-
Dostępność:
Brak
(0 szt.)
- szt.
- Cena brutto: 427,92 zł 347,90 zł
Zabezpieczenie transformatorów 3-bieg. PKZM0-1,6-T
Program
General | |||||
Standards
|
IEC/EN 60947, VDE 0660 | ||||
Climatic proofing
|
Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 |
||||
Ambient temperature
|
°C | ||||
Storage
|
°C | -25- 80 | |||
Open
|
°C | -25- 55 | |||
Enclosed
|
°C | -25- 40 | |||
Mounting position
|
|
||||
Direction of incoming supply
|
As required | ||||
Degree of protection
|
|||||
Device
|
IP20 | ||||
Terminations
|
IP00 | ||||
Protection against direct contact
|
Finger and back-of-hand proof | ||||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
|
g | 25 | |||
Altitude
|
m | 2000 | |||
Terminal capacity screw terminals
|
mm2 | ||||
Solid
|
mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|||
Flexible with ferrule to DIN 46228
|
mm2 | 1 x (1 - 6) 2 x (1 - 6) |
|||
Solid or stranded
|
AWG | 18 - 10 | |||
Specified tightening torque for terminal screws
|
|||||
Main cable
|
Nm | 1.7 | |||
Control circuit cables
|
Nm | 1 | |||
Main conducting paths | |||||
Rated impulse withstand voltage
|
Uimp | V AC | 6000 | ||
Overvoltage category/pollution degree
|
III/3 | ||||
Rated operational voltage
|
Ue | V AC | 690 | ||
Rated uninterrupted current = rated operational current
|
Iu= Ie | A | 25 or current setting of the overcurrent release | ||
Rated frequency
|
f | Hz | 40 - 60 | ||
Rated frequency
|
Hz | 40- 60 | |||
Current heat loss (3 pole at operating temperature)
|
W | 6 | |||
Lifespan, mechanical
|
Operations | x 106 | 0.1 | ||
Lifespan, electrical (AC-3 at 400 V)
|
Operations | x 106 | 0.1 | ||
Maximum operating frequency
|
Ops./h | ||||
Max. operating frequency
|
Ops/h | 40 | |||
Short-circuit rating
|
|||||
AC
|
|||||
|
→ Engineering | ||||
DC
|
|||||
Short-circuit rating
|
kA | 60 | |||
Short-circuit rating
|
60 (up to PKZM0-16) 40 (PKZM0-20 to PKZM0-32) |
||||
Motor switching capacity
|
kArms | ||||
AC-3 (up to 690 V)
|
A | 25 | |||
DC-5 (up to 250 V)
|
A | 25 (3 contacts in series) | |||
Trip blocks | |||||
Temperature compensation
|
|||||
to IEC/EN 60947, VDE 0660
|
°C | -5…40 | |||
Operating range
|
°C | -25…55 | |||
Temperature compensation residual error for T > 40 °C
|
0.25%/K | ||||
Setting range of overload releases
|
x Iu | 0.6- 1 | |||
Short-circuit release fixed
|
x Iu | 20 | |||
Fixed short-circuit release
|
Basic device 20 x Iu | ||||
Short-circuit release tolerance
|
± 20% | ||||
Phase-failure sensitivity
|
IEC/EN 60947-1-1, VDE 0660 Part 102 |
Technical data according to ETIM 4.0
Number of poles
|
3 | ||
Rated uninterrupted current Iu
|
A | 1.6 | |
Number of auxiliary contacts as N/Cs
|
0 | ||
Number of auxiliary contacts as N/Os
|
0 | ||
Device construction
|
- | ||
With under voltage release
|
No | ||
Motor operator optional
|
No | ||
Integrated earth fault protection
|
No | ||
Suitable for DIN rail (top hat rail) mounting
|
YES | ||
Setting range non-delayed short-circuit release
|
A | 32 | |
Setting range short-term delayed short-circuit release
|
A | 0 | |
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
|
kA | 150 | |
Switched-off indicator available
|
YES | ||
Type of control element
|
Rotary head | ||
Connection type main current circuit
|
Screw connection | ||
Motor operator integrated
|
YES | ||
Position of connection for main circuit
|
- | ||
Protection type (IP)
|
IP20 | ||
Number of auxiliary contacts as changeover contact
|
0 | ||
Setting range of overload releases
|
A | 1.6 |
CAD-Data
|
Additional product information (links)
IL03407010Z (AWA1210-2138) motor-protective circuit-breakers | |||
IL03407011Z (AWA1210-1925) motor-protective circuit-breaker | |||
Installation Instructions | |||
MN03402003Z-DE/EN (AWB1210-1458) Motorschutzschalter PKZM0, Überlastüberwachung von EEx e-Motoren | |||
Documentation | |||
Motor starters and "Special Purpose Ratings" for the North American market | |||
Busbar Component Adapters for modern Industrial control panels |