Moduł styków pomocniczych 1Z+3R mont.centralnie 11DILE

  • Add feedback:
  • Code: 010224
  • Availability: Exists  (5 pcs.)
  • pcs.
  • Gross price: 60.64 zł 49.30 zł

Moduł styków pomocniczych 1Z+3R mont.centralnie 11DILE

Program
Product range
    Accessories
Description
    with interlocked opposing contacts
Pole
    2 pole
Connection technique
    Screw terminals
Contacts
     
N/O = Normally open
    1 N/O
N/C = Normally closed
    1 N/C
AC-15
     
AC-15
     
220 V 230 V 240 V
Ie A 4
380 V
400 V
415 V
Ie A 2
Conv. thermal current
Ith A 10
Code number and version of combination
     
DILER-40(-G)
    51 E
DILER-31(-G)
    42
DILER-22(-G)
    33
Contact sequence
   
Can be combined with contactor
    DILEM-10(-G)(…)
DILEM-01(-G)(…)
DILEM-4(-G)(…)
DILER40(-G)
DILER31(-G)
DILER22
DILEEM-10(-G)(…)
DILEEM-01(-G)(…)
DILEM12-10(-G)(…)
DILEM12-01(-G)(…)
InstructionsContacts to EN 50005
Contacts according to EN 50012 are to be prefered.
Version E combinations correspond to EN 50011 and are to be preferred.
InstructionsNo interlocked opposing mechanism in NO early-makes and NC late-breaks.
Auxiliary contact modules with positive acting contacts
Approbationen
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29184
UL CCN NKCR
CSA File No. 012528
CSA Class No. 3211-03
NA Certification UL Listed, CSA certified
 
Auxiliary contacts
flexible with ferrule
    Yes
Rated impulse withstand voltage
Uimp V AC 6000
Overvoltage category/pollution degree
    III/3
Rated insulation voltage
Ui V AC 690
Rated operational voltage
Ue V AC 600
Safe isolation to VDE 0106 Part 101 and Part 101/A1
     
between coil and auxiliary contacts
  V AC 300
between the auxiliary contacts
  V AC 300
Rated operational current
Ie A  
AC-15
     
220/240 V
Ie A 4
60 Hz
Ie A 2
500 V
Ie A 1.5
DC L/R 15 ms
     
Contacts in series:
  A  
1
24 V A 2.5
2
60 V A 2.5
3
100 V A 1.5
3
220 V A 0.5
Conv. thermal current
Ith A 10
Control circuit reliability (at Ue= 24 V DC, Umin= 17 V, I min= 5.4 mA)
Failure rate λ <10-8, < one failure at 100 million operations
Component lifespan at Ue= 240 V
     
AC-15
Operations x 106 0.2
DC
     
Footnote
    Switch-on and switch-off conditions based on DC-13, time constant as specified
L/R = 50 ms: 2 contacts in series at Ie= 0.5 A
Operations x 106 0.15
Short-circuit rating without welding
     
Maximum overcurrent protective device
     
Short-circuit protection only
    PKZM0-4
Short-circuit protection maximum fuse
     
500 V
  A gG/gL 6
500 V
  A fast 10
Current heat loss at Ith
     
Per contact
  W 0.2
Technical data according to ETIM 4.0
Suitable for earth leakage circuit breaker
    No
Type of electric connection
    Screw connection
Rated operation current Ie at AC-15, 230 V
  A 4
Mounting type
    Front mount
Suitable for pendant switch
    No
Suitable for front element
    No
Suitable for circuit-breakers
    No
Suitable for safety position switches
    No
Suitable for step switches
    No
Suitable for pressure switch/selector switch actuator
    No
Suitable for cam switches
    No
Suitable for motor protective circuit breakers
    No
Suitable for series-mounting relays
    No
Suitable for solenoid
    No
Suitable for compact switch-disconnector
    No
Suitable for miniature circuit-breakers
    No
Suitable for pulse relay
    No
Suitable for contactor relay relay
    YES
Suitable for pendant pushbutton
    No
Suitable for residual current device
    No
Number of contacts as change-over contact
    0
Number of contacts as N/O
    1
Number of contacts as NC
    1
Suitable for impulse relays
    No
Suitable for position switches
    No
Suitable for switch-disconnector/residual current device
    No
Suitable for contactors
    YES
Suitable for installation contactor / installation relay
    YES
Characteristics
Switching duty for non-motor loads, 3-pole, 4-pole
Operating characteristics
Non-inductive or slightly inductive loads
Electrical characteristics
Make: 1 x rated current
Break: 1 x rated current
Utilization category
100 % AC-1
Typical applications
Electric heat
Short-time loading, 3-pole
Time interval between two loading cycles: 15 minutes

Opis pochodzi ze strony www.moeller.net .